Share:

Unlocking ground-source energy for major commercial development

20. October 2026 | 5 min read
Referenz Kronstorf

An ambitious logistics project is currently under construction in Kronstorf, Austria as dm-drogerie markt GmbH embark on a new 43000 m² distribution center. 

Sustainable construction is a key focus of the project, which hopes to achieve the ÖGNI Gold Standard — an Austrian certification for energy efficiency, resource conservation, and quality.

Heating and cooling with ground energy

Schwaiger Heizung-Sanitär-Lüftung GmbH from St. Johann im Pongau was commissioned to handle the entire heating, cooling, and building services installation for this project. Under the direction of Hannes Schwaiger and Werner Hacklbauer, a 270 kW heat pump and large-area ground collector pipes are being implemented for an advanced, energy-efficient heating and cooling solution.

The decision to use a ground-source heat pump system was based on their excellent energy efficiency and low operating costs — an ideal solution for buildings on large plots with ample surrounding space.

Referenz Kronstorf

How do ground source heat pump systems work?

Sometimes confused with geothermal heating systems, ground-source heat pump systems consist of buried pipes that take advantage of stable underground temperatures. A water-glycol mixture runs through the pipe network, absorbing thermal energy from the surrounding earth which remains between 8 °C and 12 °C year-round.


For heating, ground-warmed fluid travels from the pipes to a heat exchanger inside the heat pump, where its heat is transferred to a refrigerant. The refrigerant is then compressed, which raises its temperature and the additional thermal energy is transferred to the building’s heating system to disperse the warmth. 


For cooling, the cycle is reversed. In a building with hydronic cooling, warm indoor air is absorbed by fluid circulating through the hydronic pipe network. This warmed fluid travels via the heat pump into underground collector pipes where the heat dissipates due to lower ground temperatures in warm weather. The cooled fluid returns to the building’s hydronic system, absorbing more heat and lowering the room temperature.


In the dm project, the ground source heat pump system will supply a concrete core activation system, where hydronic heating and cooling pipes are integrated into the building envelope.

Referenz Kronstorf

Delivered pre-assembled and ready to connect

For the efficient distribution of thermal energy from the ground, a specially manufactured PE coiled pipe distribution shaft in DN 1600 was used. It was fully pre-assembled and delivered to the construction site in August 2025. On site, the shaft was placed on a prepared foundation, and installers were immediately able to begin laying and connecting the ground collector pipes.

This ready-to-use solution saves valuable assembly time on site and minimizes potential installation errors.

 

Distribution shaft technical data:

Length: 4670 mm

Height (including entry): 2424 mm

Equipped with:

  • Distribution pipe in DN 125 (U-shape)

  • 53 connection ports (26 or 27 per side)

  • Filling, venting and emptying unit

  • Shut-off valves, flow regulators, pressure gauges, thermometers

  • Access via ladder and secured cover
Referenz Kronstorf

Robust collector pipes for heavy loads

Other key components of the project’s ground source heat pump system are high-quality collector pipes that can be laid in various ways. Whether by trenching, milling, or excavating the soil, Pipelife collector pipes made from PE100-RC offer:

  • High crack and point load resistance

  • A long service life, even under demanding installation conditions

In this project, 15.9 km of PE100-RC DN/OD 32 mm collector pipes were laid in two layers, one on top of the other. The first layer, consisting of 27 loops, was quickly laid out on the prepared area and secured in the ground with pegs. The installation team had to ensure sufficient slack in the pipes to accommodate temperature fluctuations.

After successful pressure testing of the first layer, a 70 cm layer of soil was applied on top followed by the second layer of collector pipes, consisting of 26 loops. This layer was also pressure tested after completion.

Referenz Kronstorf

Secure connections thanks to ELGEF Plus

For connecting the collector pipes to the flow and return lines of the manifold, 106 high-quality +GF+ electrofusion couplings (ELGEF Plus) were used. The proven welding technology ensures safe installation and maximum operational reliability.

Referenz Kronstorf - Werner Hacklbauer Fa. Schwaiger

A reliable partner

The collaboration with Pipelife was excellent on this project as well. Ronnie Rauter provided us with outstanding on-site support, and the Pipelife engineers offered invaluable assistance with planning and design. For projects of this scale, it is extremely important to be able to rely on your partner, and that is absolutely the case with Pipelife.

Werner Hacklbauer

Project Manager Schwaiger Heating-Plumbing-Ventilation GmbH

 

Construction on the dm distribution center began in summer 2025 and is scheduled for completion and outfitting by the end of 2027. Commissioning is planned for the summer of 2028.